Customization: | Available |
---|---|
Transport Package: | Plywood Case |
Origin: | China |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The circuit breaker is mainly used for GIS. The product adopts the splint structure, and has the advantages of simple installation, reliable breaking performance, long service life and maintenance-free, and is an ideal substitute for the vacuum circuit breaker for GIS. Product performance meets the requirements of GB1984-2014 "AC high voltage circuit breaker" E2-M2-C2 circuit breaker.
Technical parameters
Item |
Unit |
Value |
|
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
Rated current |
A |
630 |
4 |
Rated short time withstand current |
kA |
20/25 |
5 |
Rated peak withstand current |
kA |
50 |
6 |
Rated short circuit duration |
s |
4 |
7 |
Rated short circuit making current |
kA |
50 |
8 |
Mechnical life |
times |
10000 |
9 |
Main loop resistance |
μΩ |
≤60 |
10 |
1 min power frequency withstand voltage |
kV |
38(in air) |
Applying ambient condition
1. Altitude above sea level: no more than 2000m, earthquake intensity not exceed 8 degrees.
2. Ambient temperature: Max. Temperature: +50ºC, Min. Temperature: -45ºC. Average relative humidity daily: ≤95%, average relative humidity monthly: ≤90%.
3. It should be installed in condition without obvious dust, fire, chemical erosion, explosion, vapor and salt spray.
4. Rated SF6 gas pressure: 0.04mPa. SF6 gas meets the requirements of GB/T 12022-2014 "Industrial sulfur hexafluoride"
Overall outline drawing of VS1-12P/T