Customization: | Available |
---|---|
Type: | Power |
Certification: | ISO9001:2000 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
KYN28-12(Z) Indoor HV Vacuum Switchgear
No. | Name | Unit | Data | |
1 | Rated voltage | kV | 3.6 7.2 12 | |
2 | Rated current | A | 630 1250 1600 2000 2500 3150 4000 | |
3 | Rated frequency | Hz | 50 | |
4 | Rated short time withstand current | kA | 16 20 25 31.5 40 50 | |
5 | Rated peak withstand current | 40 50 63 80 100 125 | ||
6 | Rated power frequency withstand voltage | Pole to pole, pole to earth |
kV | 42/1min |
Across nterrupter | 48/1min | |||
7 | Rated lightning impulse withstand voltage | Pole to pole, pole to earth |
75 | |
Across nterrupter | 85 | |||
8 | Rated short-time duration | S | 4 | |
9 | Degree of Protection | IP4X |
No. | Name | Unit | Data | ||
1 | Rated voltage | kV | 3.6 7.2 12 | ||
2 | Rated current | A | 630 1250 1600 2000 2500 3150 4000 | ||
3 | Rated short circuit breaking current | kA | 16 20 25 31.5 40 50 | ||
4 | Rated short-time withstand current | 16 20 25 31.5 40 50 | |||
5 | Rated peak withstand current | 40 50 63 80 100 125 | |||
6 | Rated power frequency withstand voltage | Pole-to-pole, Pole-to-earth |
kV | 42/1min | |
Across nterrupter | 48/1min | ||||
7 | Rated lightning impulse withstand voltage | Pole-to-pole, Pole-to-earth |
75 | ||
Across nterrupter | 85 | ||||
8 | Rated short-time duration | S | 4 | ||
9 | Opening time | ms | 20≤t≤65 | ||
10 | Closing time | ms | 20≤t≤75 | ||
11 | Breaking operations of rated short circuit- breaking current | Cycle | 30(≤31.5kA) | 20(≥40kA) | |
12 | Mechanical endurance | Cycle | 20000(≤31.5kA) 10000(≥40kA) |
Name | Unit | Data | |
Rated operating voltage | Opening coil | V | DC220/110 AC220/110 |
Closing coil | |||
Power of coil | Opening coil | W or VA | 245 |
Closing coil | |||
Power of energy-stored motor | W | 50 | |
Rated voltage of energy-stored motor | V | DC220/110 AC220/110 | |
Charging time | S | ≤10 |
Height | 2350 | |
Width | Rated current of small branch bus-bar is 1250A and the below shrt-circuit breakingcurrent is 31.5KA | 800 |
Rated current of small branch bus-bar is 1600A and above | 1000 | |
Depth | Cale In-(out) | 1500 |
Overhead In-(out) | 1660 | |
Weight(kg) 800~1200 |
Width | Depth | M | N | L |
800 | 1500 cable | 630 | 800 | 1450 |
1660 overhead | 1610 | |||
1000 | 1500 cable | 830 | 1000 | 1450 |
1660 overhead | 1610 |
Q: Could I have prices of your products?
A: Welcome. Please feel free to send us inquiry here. We will reply you within 24 hours
Q: Can l get a sample before the bulk order?
A: Yes, we welcome sample order to test and check quality. Mixed samples are acceptable.
Q: Can we print our logo/ company name on products?
A: Yes, of course, we accept OEM, then need you to provide brand authorization to us
Q:Do you accept product customization?
A: Yes, of course, please provide specific drawings or parameters, we will quote you after evaluation
Q: What is the lead time?
A: The lead time depends on the quantities ordered, generally within 7-20 days after receiving the payment.
Q: What is your Trade Terms?
A: We accept EXW, FOB, CIF, FCA, etc.
Q: What is your payment method?
A: We accept T/T, Western Union, Paypal, irrevocable L/C at sight, etc
Q: Do you inspect the finished products?
A: Yes, each step of production and finished products wil be came out inspection by Qc department before shipping. And we willprovide goods inspection reports for your reference before shipment
Q: How to solve the quality problems after sales?
A: Take photos of the quality problems and send to us for our checking and confirming, we will make a satisfied solution for you within 3 days.