Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear

Product Details
Customization: Available
Type: Power
Certification: ISO9001:2000
Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

  • Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear
  • Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear
  • Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear
  • Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear
  • Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear
  • Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear
Find Similar Products
  • Overview
  • Product Description
  • FAQ
Overview

Basic Info.

Model NO.
KYN61-40.5kV
Operation Voltage
High Voltage
Size
3 Uint
Application Range
Power Plants
Shell Material
Steel Plate
Brand
Joyelectric
Rated Voltage
40.5kv
Rated Current
1250, 1600, 2000A
Rated Frequency
50Hz
Rated Short Time Withstand Current
20, 25, 31.5ka
Transport Package
Plywood Case
Trademark
JET
Origin
China
HS Code
85352100

Product Description

Product Description

KYN61-40.5(Z) Indoor HV Vacuum Switchgear
Main charateristics
  1. The switchgear is as assembly type. The circuit breaker is floor roll-out.Adopted new compound insulation, vacuum circuit breaker has the features of good interchange ability and easy replacement.The truck shelf is equipped with lead-screw drive mechanism, which can move truck easily and prevent the mechanism be damaged from faulty operation. All the operations can be done with the door shut.All interlocks connecting with the main switch, truck and door of switchgear adopt compulsive mechanical lock and can meet the requirement of "FIVE PREVENTION".The space of the cable compartment is abundant for the connection of several cables.The instant earthing switch is used for earthing and short-circuiting of the circuit.The degree of protection for the enclosure is IP3X.It is IP2X when the door of truck compartment open.It conforms to GB3906-1990.DL404-1997 and refers to IEC-298 standard.
Applying ambient conditions
Ambient temperature: The max. temperature should below +40ºC.The average value n 24 hours should be no more than 35ºC. The min .temperature should above -10ºC.
The height above sea level should be no higher than 1000m.
Relative humidity: The average humidity of a day should be no more than 95%.The average humidity of a month should be no more than 90%.
Water vapour pressure: The average vapour pressure of a day should be more than 2.2kPa. The average vapour pressure of a month should be no more than 1.8kPa.
It should be used in the place where it is free from fire, explosion, serious fifth, chemical erosion and vibration.
Main Technical Data of the Vacuum Switchgear
No. Name Unit Data
1 Rated voltage kV 40.5
2 Rated current A 1250, 1600, 2000
3 Rated frequency Hz 50
4 Rated short time withstand current kA 20, 25, 31.5
5 Rated peak withstand current kA 50, 63, 80
6 Rated power frequency withstand voltage kV 95/1min
7 Rated lightning impulse withstand voltage kV 185
8 Rated duration of short circuit S 4
9 The degree of protection   IP3X
Main Technical Data of the Vacuum Circuit Breaker
No. Name Unit Data
1 Rated voltage kV 40.5
2 Rated frequency Hz 50
3 Rated power frequency withstand voltage kV 95/1min
4 Rated lightning impulse withstand voltage kV 185
5 Rated current A 1250, 1600, 2000
6 Rated short time withstand current kA 20, 25, 31.5
7 Rated short circuit breaking current kA 20, 25, 31.5
8 Rated peak withstand current kA 50, 63, 80
9 Rated duration of short circuit S 4
10 Opening time ms 30≤t≤60
11 Closing time ms 50≤t≤100
12 Breaking times of the rated short circui breaking current Cycle 20
13 Mechanical endurance Cycle 10000
Main Technical Data of Spring Operating Mechanism
Name Unit Data
Rated operating voltage Opening coil V DC220/110  AC220/110
Closing coil
Rated operating current Opening coil A 0.96(220V)  1.05(110V)
Closing coil
Power of energy-stored motor W 230
Rated voltage of energy-stored motor V DC220/110  AC220/110
Duration for storing energy S ≤12

Structure
Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear


Overall dimesion of the switchgear
Width×Depth×Height: 1400×2800×2600mm

Kyn61 40.5kv High Voltage Indoor AC Metal Electric Enclosure Distribution Switchgear
FAQ

Q: Could I have prices of your products?
A: Welcome. Please feel free to send us inquiry here. We will reply you within 24 hours
Q: Can l get a sample before the bulk order?
A: Yes, we welcome sample order to test and check quality. Mixed samples are acceptable.
Q: Can we print our logo/ company name on products?
A: Yes, of course, we accept OEM, then need you to provide brand authorization to us
Q:Do you accept product customization?
A: Yes, of course, please provide specific drawings or parameters, we will quote you after evaluation
Q: What is the lead time?
A: The lead time depends on the quantities ordered, generally within 7-20 days after receiving the payment.
Q: What is your Trade Terms?
A: We accept EXW, FOB, CIF, FCA, etc.
Q: What is your payment method?
A: We accept T/T, Western Union, Paypal, irrevocable L/C at sight, etc
Q: Do you inspect the finished products?
A: Yes, each step of production and finished products wil be came out inspection by Qc department before shipping. And we willprovide goods inspection reports for your reference before shipment
Q: How to solve the quality problems after sales?
A: Take photos of the quality problems and send to us for our checking and confirming, we will make a satisfied solution for you within 3 days.
 


 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier